WirelessHART Fieldgate SWG70 11 Additional Functions
Endress+Hauser 75
11 Additional Functions
Additional Functions contains a number of functions which maybe required during the Fieldgate
life-cycle but not for everyday operation. The functions offered depend upon the parametrization
tool. In FieldCare the corresponding function is called by right-clicking on the Fieldgate SWG70
node and selecting Additional Functions.
11.1 Reset
Reset allows the Fieldgate, the instrument list and the network to be reset, see table. The reset is
intiated by pressing the appropriate button. During reset, communication with the network will be
temporarily lost.
1 Click on the Additional Functions> Reset leaf to open the dialogue:
The significance of the parameters is described in the table below
Reset options
11.2 Self Test
Self test invokes a self testing procedure for Fieldgate SWG70.
1 Click on the Additional Functions> Self Test leaf to open the dialogue:
2 Press the Perform Self Test button to start the test
3 The results can be seen in the first two sections of the HART diagnosis dialogue:
Diagnostics =>Wired Communication =>HART dialog, Chapter 9.3.2
Parameter group Meaning
Device Reset Press this button to restart Fieldgate without any impact on the established network.
Fieldgate SWG70 is restarted with all user settings intact
Rebuild Instrument List Press this button to regenerate the instrument list
Create a backup of the existing instrument list before resetting, see Chapter 8.6.8
The existing instrument list is overwritten.
The Modbus addresses of the devices in the network may change
Reform Network Press this button to restart and reestablish the network.
The existing instrument list is overwritten.
The Modbus addresses of the devices in the network may change
Depending on the size of the network, this process may take some minutes
Reset Diagnosis Bits Press this button to reset the diagnosis bits in Fieldgate SWG70